A green tile is not acceptance

Original diagram. Not a site record.
Installed is not accepted. A screen can be on, and green, and still have no clock, no quality mark, and no forced failure on this image. You may accept a named list of points that passed. You do not accept "the platform." Strike that sentence. Their identifiers stay in their file. Your note says the human name, the sentence, and that the proof exists.
A design kilowatt on that screen is not today's load. It does not fill the used-capacity cell because the measured point is stale. Stale refuses the cell. A closed breaker is not a load. A redundancy graphic is not a test of remaining capacity.
A drawing renamed as-built is still the design until someone checked it against the plant after the last change your sentence depends on. Floor and drawing disagree: write both. Do not average them into a signature.
A model without a walked measurement is a picture. File it. Do not sign airflow proved. A heat curve without a file judgment is a plot. File it. Do not sign heat proved.