One liquid system at a time

Original diagram. Not a site record.
A liquid hall is more than one machine sharing pipes. If you heat the whole hall before one system has shown it can run, a failure has too many owners. The landed order that survives without site names is simple: survey, static checks, one system at a time, a no-heat pump curve, then the heat scripts, then shutdown, then the report.
The no-heat curve matters. It tells you the pumps and the path before energy confuses the picture. Skipping it because the schedule wants heat is how a flow problem is discovered as a temperature problem.
An open fail blocks the next stage. "We will watch it during heat" is not a close. It is a decision to run later with a known defect, and it needs a waiver that says what you will do if the defect appears under heat. A waiver without that sentence is permission to be surprised.
Do not mix a bad file with a plant fail. If the load bank file is not a valid test, that is not yet a punch item against the constructor. Separate the owners before you write the line.
From Finish a Liquid Cooling Verification, Tristan, Data Center Field Guides. No store link until the Kindle edition is listed.
Related: A hit is a time, not a pass.